CSA B140.1 Series:22
- standard by CSA Group, 07/05/2022
- Atomizing- and vapourizing-type oil burners, Includes Errata (2022)
- Category: CSA GROUP
$250.00
$125.00
Full Description
Preface
This is the first edition of the CSA B140.1 Series, Atomizing- and vapourizing-type oil burners. It replaces the following CSA Group Standards: a) CSA B140.1:66, Vapourizing-type oil burners; b) CSA B140.2.1:10, Atomizing-type oil burners; and c) CSA B140.2.2:71, Pressure atomizing oil burner nozzles. The above-mentioned Standards have been amalgamated with the intent to create a single document providing requirements for oil burner construction and performance, as well as requirements for oil burner components.
This Series contains two Standards:
- CSA B140.1.1 - Atomizing-type oil burners, which consists of the requirements from CSA B140.2.1 (atomizing-type oil burners) and CSA B140.2.2 (pressure atomizing oil burner nozzles); and
- CSA B140.1.2 - Vapourizing-type oil burners, which includes the requirements from CSA B140.1 (vapourizing-type oil burners). This Standard should be read in conjunction with CSA B140.0, Oil-burning equipment: General requirements. The major changes from the previous editions of CSA B140.2.1 and CSA B140.2.2, now designated CSA B140.1.1, include the following:
- throughout the Standard, some rewording has been done for clarity;
- the scope has been expanded to include the requirements for atomizing nozzles, tubes, and cups (Clause 5.13);
- new definitions have been added;
- the requirement for electrical features has been updated to reference CSA C22.2 No. 60335-2-102, which replaces CSA C22.2 No. 3;
- a new requirement for automatic electrical burner control systems has been added to comply with the requirements of ANSI Z21.20
- CAN/CSA-C22.2 No. 60730-2-5;
- tables have been relocated from the end of the Standard to the applicable clause;
- the Clause 5.13.2 on atomizing nozzles now includes the requirements from CSA B140.2.2, with the following major changes:
- the clause title has been changed from "Pressure atomizing oil burner nozzles" to "Atomizing nozzles";
- the notes regarding markings on the nozzles have been deleted; and
- SI (metric) units have been added;
- the following changes have been made to Table 2:
- the times for the trial for ignition period and the flame failure response time for appliances with an input rate less than or equal to 11.4 L/h (3.0 US gph) have been divided into two categories: one with an input rate less than or equal to 3.78 L/h (1.0 US gph) and one with an input rate >3.78 L/h (1.0 US gph) and less than or equal to 11.4 L/h (3.0 US gph);
- the flame failure response time for some appliances with an input rate between 11.4 L/h (3.0 US gph) and 26.5 L/h (7.0 US gph) has been changed from 3 to 4 s; and
- the flame failure response time for appliances with an input rate > 26.5 L/h (7.0 US gph) and less than or equal to 76 L/h (20.0 US gph) has been changed from 3 to 4 s;
- when testing pumps, the grade of fuel(s) required to be used is now the grade for which the pump is designed or intended. Previously, the lightest-grade fuel with the lowest viscosity was required to be used;
- the clause on alternate fuel grades for testing has been deleted. Clause 6.8.14 has been added for wetted seals and gaskets exposed to grade B6-B20;
- the method of test for hydrostatic pressure leakage has been changed;
- the pressure that components of fuel pumps or units are subjected to during the static pressure leakage test has been changed;
- the mercurous nitrate immersion test procedure now references UL 125 instead of ASTM B154;
- the test voltages for ignition have been changed from actual values to a percentage of the nominal voltage. Actual voltage has not changed;
- the timings for flame failure response time have been provided in Table 2 only; and
- the marking requirements have been changed to comply with CSA C22.2 No. 60355-2-102 instead of CSA C22.2 No. 3. The major changes from the previous edition of CSA B140.1, now designated CSA B140.1.2, include the following:
- throughout the Standard, some rewording has been done for clarity;
- some of the caution statements for labels have been reworded;
- new definitions have been added;
- the maximum input rate for vapourizing-type oil burners has been limited to 4.5 L/h (1.2 US gph). Previously, it was unlimited;
- the requirement for electrical features has been updated to reference CSA C22.2 No. 60335-2-102, which replaces CSA C22.2 No. 3;
- a new requirement has been added that strainers comply with UL 331;
- new requirements have been added for constant levelling devices;
- new requirements have been added for manually lighted burners;
- a maximum time limit of 5 min has been added for th
Product Details
- Edition:
- 1st
- Published:
- 07/05/2022
- ISBN(s):
- 9781488342271
- Number of Pages:
- 74
- File Size:
- 1 file , 940 KB
- Product Code(s):
- 2429940, 2429941, 2429940, 2429941
- Note:
- This product is unavailable in Russia, Ukraine, Belarus
CSA ANSI Z21.60b-2004/CSA 2.26b-2004
Addenda 2 to ANSI Z21.60-2003/CSA 2.26-2003, Decorative Gas Appliances for Installation in Solid-Fue..
$66.00 $132.00
CSA C22.2 NO. 43-04
Lampholders (Bi-National standard, with UL 496). Includes Update No. 1 (2006)..
$113.00 $226.00
CSA C22.2 NO. 250.0-04
Luminaires (Bi-National standard, with UL 1598), Includes Updates No. 1 and No. 2 (2007)..
$313.00 $625.00